Commercial Refrigeration Servicing & Repair in London
Planned servicing, breakdown repair and F-Gas leak checks for cold rooms, walk-in freezers and chillers. F-Gas certified engineers, a clear price before work starts, and a 24/7 emergency line for when it fails at night.
REFCOM F-Gas certified REF102416824/7 emergency line, nights includedsame-day response in London
Mainteniq services and repairs commercial refrigeration across London and the Home Counties: cold rooms, walk-in freezers and chillers for restaurants, hotels, food businesses and office buildings.
- Our engineers hold REFCOM F-Gas company certification REF1024168, which covers stationary refrigeration, air conditioning and heat pump equipment, so leak checks, refrigerant top-ups and repairs are done legally and written into your F-Gas record.
- Every visit ends with a written report, and refrigeration can sit on the same planned maintenance contract as your air conditioning, heating and ventilation.
Commercial Refrigeration Services
Servicing that stops the breakdown, and repair when it happens anyway.
Planned refrigeration servicing
Scheduled visits for cold rooms, walk-in freezers and chillers: condenser and evaporator coils cleaned, fans, drains, defrost and controls checked, temperatures recorded, and a written engineer report after every visit.
Breakdown repair
Fault finding and repair when a cold room is warming up, a freezer is icing over, a compressor keeps tripping or the controller is showing alarms. Refrigerant work is carried out by F-Gas certified engineers.
F-Gas leak checks and records
Leak checks at the intervals the F-Gas rules set for your equipment, with every check, top-up and repair written into the equipment record you are required to keep.
Door seals, heaters and panels
Worn door gaskets, failed door heaters, frozen thresholds and damaged panel joints are where cold rooms lose most of their cold. We find and fix them on the routine visit.
Condensers and coils
Blocked condenser coils make a system run hot, use more power and fail in summer. Coil cleaning is part of every service, not an extra.
Temperature checks for your records
Probe readings checked against the controller display on each visit, so the temperatures in your food safety records can be trusted.
Signs Your Cold Room or Freezer Needs an Engineer
Most refrigeration breakdowns give a warning first. These are the ones our customers describe when they call.
- The cold room or walk-in freezer is slowly warming up and nobody knows why
- Ice building up on the evaporator, the floor or around the door
- Water pooling inside the cold room or dripping from the evaporator
- The compressor running non-stop, short cycling or tripping
- Door that will not close properly or a split, flattened seal
- Temperature alarms going off overnight or at weekends
- The system needing a refrigerant top-up again and again
- Readings on the display that do not match your own probe

Why Do Cold Rooms and Freezers Break Down?
Usually because of dirt, ice and wear rather than a sudden failure: a blocked condenser coil, an iced-up evaporator, a split door seal or a slow refrigerant leak makes the system work harder every week until the compressor gives up.
Condenser coils on the outdoor or roof-mounted unit pick up grease, leaves and dust, so the system cannot reject heat and runs hotter and longer, which is why so many cold rooms fail on the first hot day of summer.
- Inside, a door that does not seal lets warm, moist air in, and that moisture freezes on the evaporator coil until air can no longer pass through it.
- A blocked drain line turns the defrost water into ice on the floor.
- A small refrigerant leak means the system slowly loses capacity, gets topped up, and leaks again.
- Planned servicing finds all of these while they are cheap to fix.
How Often Does Commercial Refrigeration Need Leak Checking?
It depends on how much refrigerant the system holds, measured in tonnes of CO2 equivalent. Under the F-Gas rules that apply in Great Britain, equipment from 5 tonnes up to 50 tonnes CO2e must be leak checked at least every 12 months, from 50 to 500 tonnes every 6 months, and 500 tonnes or more every 3 months.
Fitting an automatic leak detection system doubles those intervals (to 24, 12 and 6 months), and systems of 500 tonnes CO2e or more must have one.
- The operator of the equipment, usually the business using it, is responsible for making sure the checks happen and for keeping records of the refrigerant, the checks and any repairs.
- We work out which band each of your systems falls into, set the leak check schedule to match, and keep the record up to date on every visit.
- See our F-Gas compliance page for the full picture, including air conditioning.
Why Is My Cold Room Icing Up?
Ice in a cold room or walk-in freezer almost always means warm, damp air is getting in or the defrost is not doing its job: a worn door seal, a door left open, a failed door heater, a defrost heater or timer fault, or a blocked drain.
Chipping the ice off treats the symptom and can damage the coil. We find the cause, fix the seal, heater, defrost setting or drain, and check the coil and fans afterwards so the room holds temperature again.
What Happens If It Fails at Night?
Call our 24/7 emergency line. It is answered at night and at weekends, and in London we aim to have an engineer with you the same day.
Outside London, across the Home Counties, attendance is usually within a day.
- While you wait, keep the door shut, move the most valuable stock to another cold store if you have one, and keep recording the temperature so you know what can be kept.
- Contract customers are prioritised. For air conditioning and heating breakdowns, see emergency HVAC repair.
How a Refrigeration Visit Works
Tell us the equipment
Cold room, walk-in freezer or chiller, the make if you know it, and what it is doing. A photo of the controller or the data plate on WhatsApp helps.
Engineer visit
An F-Gas certified engineer checks the whole system: condensing unit, evaporator, door, drains, controls and refrigerant circuit.
Clear findings and price
You get the fault, the fix and the price before any work starts. Nothing is guessed over the phone.
Fixed and recorded
We repair it, log any refrigerant work in your F-Gas record and leave a written report. Planned servicing from there if you want it.
Who We Look After Refrigeration For
Restaurants and commercial kitchens
A cold room failing overnight can mean throwing away a whole delivery. Planned servicing keeps coils, seals and drains in order so it does not happen on a Friday night.
Hotels and serviced apartments
Kitchen cold rooms, walk-in freezers and the air conditioning looked after by one contractor, on one schedule.
Retail and food businesses
Walk-in chillers and freezers kept at temperature, with the records your food safety checks rely on.
Offices and building managers
Staff kitchens, catering areas and chillers serving the building, maintained alongside the rest of the plant.
Also need the rest of the plant covered? Air conditioning, HVAC and air handling unit maintenance and heat pump servicing.
Book Refrigeration Servicing or a Repair
Send us the equipment and what it is doing on WhatsApp, or call the 24/7 line. You get a clear price before any work starts and a written report after.
Want it on a contract with everything else? See planned maintenance contracts